MGE Galaxy 7000 GFC Shore Connect 500KvA

Performance 3 phase power protection specially designed for shore connection application, max capability up to 10 products in parallel.

Includes: Installation guide , Service Manual

G7TQ500CSFeatures

MGE Galaxy 7000 GFC Shore Connect 500KvA

  • Audible alarms
    Provides notification of changing utility power and UPS power conditions
  • Auto recognition of external batteries
    UPS recognizes when external battery packs are attached and automatically adjusts runtime.
  • Automatic internal bypass
    Supplies utility power to the connected loads in the event of a UPS power overload or fault.
  • Configurable for N+1 internal redundancy
    Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
  • Double conversion on-line topology
    Guarantees a consistently high level of power quality. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.
  • Dual mains input
    Increases availability by allowing the UPS to be connected to two separate power sources.
  • Manual maintenance bypass
    Reduces installation costs by eliminating the need for an external mechanical bypass.

Galaxy 7000Features & Benefits

Compatibility
  • Parallel capability
    Multiple units can be placed in parallel to meet power capacity and redundancy requirements
  • Output synchronization to external source
    UPS systems can be synchronized with any other independent source for use with downstream static transfer switches.
  • Compatible with Schneider Electric's lithium ion battery solution
    Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictablity and manageability.
 
Economy
  • Advanced electrical features
    Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency
  • ECO Mode
    Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
  • Fully-rated power kVA equals kW
    Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
 
Manageability
  • Network management capability
    Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet.
 
Sustainability
  • EU CoC for UPS
    Ensures that UPSs sold in the EU are highly efficient
 
Availability
  • High availability architecture
    Different running modes : hot stand-by, integrated parallel, or centralized static switch for multi-modules leading to availability architectures

    Output

    • Output power capacity
      450.0 KWatts / 500.0 kVA
    • Max Configurable Power (Watts)
      450.0 KWatts / 500.0 kVA
    • Nominal Output Voltage
      400V 3PH
    • Neutral Output Current
      938A
    • Output Voltage Note
      Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
    • Output Voltage Distortion
      Less than 2%
    • Output Frequency (sync to mains)
      50 Hz, 60 Hz
    • Output Frequency (not synced)
      60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
    • Other Output Voltages
      380, 415, 440
    • Load Crest Factor
      2.5 : 1
    • Topology
      Double Conversion Online
    • Waveform type
      Sine wave
    • Maximum Output Current
      2369
    • Output Connections
      (1) Hard Wire 4-wire (3PH + N) (Battery Backup)
      (1) Hard Wire 3-wire (3PH) (Battery Backup)
      (1) Hard Wire 4-wire (3PH - PEN) (Battery Backup)
      (1) Hard Wire 4-wire (3PH + G) (Battery Backup)
      (1) Hard Wire 5-wire (3PH + N + G) (Battery Backup)
    • Output Voltage THD
      < 2% linear load and <3% non-linear load
    • Bypass
      Built-in Maintenance Bypass

    Input

    • Nominal Input Voltage
      400V 3PH
    • Input frequency
      45 - 65 Hz
    • Input Connections
      Hard Wire 5-wire (3PH + N + G)
    • Input voltage range for main operations
      340 - 460 (400V)V
    • Input Total Harmonic Distortion
      Less than 3% for full load
    • Type of Input Protection Required
      3-pole breaker
    • Other Input Voltages
      380, 415, 450
    • Maximum Short Circuit Withstand (Icw)
      200.0kAmps
    • Maximum Input Current
      735.0A
    • Input Power Factor at Full Load
      1.0

    Batteries & Runtime

    • Battery type
      VRLA
    • Efficiency

     

     

    Communications & Management

    • Pre-Installed SmartSlot™ Cards
      AP9635CH
    • Control panel
      Multi-function LCD status and control console
    • Audible Alarm
      Audible and visible alarms prioritized by severity
    • Emergency Power Off (EPO)
      Yes
    • Available SmartSlot™ Interface Quantity
      1

    Physical

    • Maximum Height
      1900mm , 190.0cm
    • Maximum Width
      1812mm , 181.2cm
    • Maximum Depth
      855mm , 85.5cm
    • Net Weight
      1470.0kg
    • Shipping weight
      1490.0kg
    • Shipping Height
      2030mm , 203.0cm
    • Shipping Width
      1920mm , 192.0cm
    • Shipping Depth
      960mm , 96.0cm
    • Color
      Grey
    • # of Layers per Pallet
      1.0
    • # of Units per Layer per Pallet
      1.0

    Environmental

    • Operating Environment
      0 - 35 °C
    • Operating Relative Humidity
      20 - 80 %
    • Operating Elevation
      0-999.9meters
    • Storage Temperature
      -25 - 40 °C
    • Storage Relative Humidity
      20 - 80 %
    • Storage Elevation
      0-9000meters
    • Audible noise at 1 meter from surface of unit
      72.0dBA
    • Protection Class
      IP 20

    Conformance

    • Approvals
      CE, EN 60950, EN/IEC 62040-2, EN/IEC 62040-3, ISO 14001, ISO 9001, LCIE, VFI-SS-111
    • Standard warranty
      1 year repair or replace

    Sustainable Offer Status

    • Battery Directive
      Compliant
    • Battery Notes
      ts_Battery_Notes

    General

    • Bypass Connection
      4 wire (3Ph + N) or 5 wire (3Ph + N + G)
    • Bypass Protection Device
      800.0
    • Max Bypass Input Current
      844.0A

     

 